01264 387370

500kW Chiller

500kW Chiller

Summary
Specification

The 500kW chillers is the second largest individual unit in the All Seasons Hire range. With dual refrigerant circuits there is resilience built in, with the chiller able to continue operation with a fault on one circuit.

Despite this units overall size the sturdy steel constructed frame enables easy listing and positioning with 6 lifting points and fork lift pockets.

Cooling Duty 500 kW
Inlet Temperature +12°C
Outlet Temperature +7°C
Ambient +30°C
Compressor Power 202.8 kW
EER 2.5
Compressors 6
Compressor Type Scroll
Capacity Steps 6
Refrigerant Type R410a
No. of Circuits 2
Sound Pressure 60dBA @ 10m
Evaporator Type Plate
Number of Circuits 2
Design Flow 82.7 m³/h
Pressure Drop 35 kPa
Max System Pressure 208 kPa
Fan Quantity 8
Fan Type Axial
Air Max Volume 15.5 m³/s
Power Supply 415vAC 3Ø, N + Eth
Full Load Amps 394 Amps
Start Amps 648 Amps
Connection Hardwired

Get more information and stay informed

Contact us directly on 01264 387370 or email us on info@allseasonshire.com. Alternatively fill out the box to the right and we will send you more Information.