01264 387370

600kW Burner – Gas

600kW Burner – Gas

Summary
Specification

Monoblock Forced Draught Natural Gas Burner

– Fully automatic two stage operation
– Air suction circuit lined with sound proofing material
– Fan with reverse curve blades
– Air damper for air flow setting
– Butterfly valve for fuel outout regulation
– Variable cam servomotor
– Starting motor at 2800 rpm
– Housing Cooling System with high thermal insulation
– Minimum air pressure switch
– Microprocessor burner safety control box with diagnostics
– Burner on/off selection switch
– 1st – 2nd stage manual switch
– Flame inspection window
– Radio interference protection filter
– IP X0D (IP 40) electric protection level

Burner Operation Mode Two Stage Progressive
Modulation Ratio at Max Output 2÷1
Servomotor Type LKS210
Servomotor Run Time 15 Seconds
Heat Output 192/465-814 kW
Heat Output 165/400-700 Mcal/h
Efficiency 90%
Working Temperature 0-40 °C
Net Calorific Value G20 Gas 10 kWh/Nm³
G20 Gas Density 0.71 kg/Nm³
G20 Gas Delivery 19/46.5-81.4 Nm³/h
Net Calorific Value G25 Gas 8.6 kWh/Nm³
G25 Gas Density 0.78 kg/Nm³
G25 Gas Delivery 22/54-95 Nm³/h
Net Calorific Value LPG Gas 25.8 KWh/Nm³
LPG Gas Density 2.02 kg/Nm³
LPG Gas Delivery 7.4/18-32 Nm³/h
Fan Type Centrifugal with Reverse Curve Blades
Electrical Supply 3ph 50Hz 230-400v
Auxiliary Electrical Supply 1ph 50Hz 230v
Control Box RMG
Total Electrical Power 1.4 kW
Auxiliary Electrical Power 0.3 kW
Protection Level IP 44
Motor Electrical Power 1.1 kW
Rated Motor Current 4.8-2.8 A
Motor Start Up Current 25-14.6 A
Motor Protection Level IP 54
Ignition Transformer V1 – V2 230v – 1×8 kV
Ignition Transformer I1 – I2 1A – 20 mA
Sound Pressure 75 dB(A)
CO Emission <40 mg/kWh
NOx Emission <130 mg/kWh
Conforming to EN 676
Certification CE 0085AP0944
Dimensions (WxLxH) 511 x 840 x 555mm